防爆(bao)正壓櫃(gui)斷路(lu)器位置紅(hong)綠(lv)燈(deng)不(bu)亮(liang)(總控(kong)制電(dian)路(lu)斷開(kai))
檢查(zha)控(kong)制電(dian)源是否斷開(kai)(安全)和(he)閉合(he)(接(jie)觸(chu))良好
檢(jian)查(zha)控(kong)制電(dian)源兩(liang)端電(dian)壓(ya)是(shi)否(fou)正(zheng)常

防爆插(cha)座無(wu)電(dian)壓(ya)
1.為空(kong)開(kai)(保)故(gu)障,需要更(geng)換空開(保);若兩(liang)端無(wu)電(dian)壓(ya),檢(jian)查(zha)直流屏上10KV控(kong)制電(dian)源相關(guan)空(kong)開關(guan)是(shi)否處於閉合(he)位置,,電(dian)壓(ya)是(shi)否(fou)正(zheng)常。
2.防爆正(zheng)壓櫃(gui)開關(guan)是(shi)否處於試(shi)驗或工(gong)作位置,二次插頭插(cha)入(ru)是否(fou)良好。
防(fang)爆(bao)正壓(ya)櫃(gui)斷路(lu)器合(he)閘(zha)故(gu)障(拒合(he)閘(zha))
1.檢查(zha)合(he)閘(zha)電(dian)源是否分(安全)合(he)(接(jie)觸(chu))良好
2.檢(jian)查(zha)合(he)閘(zha)電(dian)源電(dian)壓(ya)兩(liang)端電(dian)壓(ya)是(shi)否(fou)正(zheng)常:出線(xian)端子(zi)無(wu)電(dian)壓(ya)的(de),為空(kong)開(kai)(保)故(gu)障,需要更(geng)換空開(保),若兩(liang)端無(wu)電(dian)壓(ya),檢(jian)查(zha)直流屏上10KV合(he)閘(zha)電(dian)源相關(guan)空(kong)開關(guan)是(shi)否處於合(he)閘(zha)位置;電(dian)壓(ya)是(shi)否(fou)正(zheng)常
3.檢查(zha)位置切換手柄是否(fou)處於工(gong)作位置
4.檢(jian)查(zha)斷路(lu)器的遠近(jin)控(kong)制開(kai)關(guan)位置是(shi)否(fou)正(zheng)確
5.檢查(zha)彈簧(huang)結(jie)構是否有(you)儲(chu)能
6.檢查(zha)斷路(lu)器連桿(gan)是(shi)否出現(xian)斷裂(lie)或變形(xing)
出現(xian)以上故(gu)障請進(jin)行(xing)處理(li)